Condenser used should conform to the following provisions:
1, using water cooling condenser when the condensing temperature not exceeding 39 degrees Celsius; with the use of evaporative condenser, the evaporation temperature of not more than 36 DEG c..
2, a condenser cooling water inlet temperature difference, the vertical shell and tube type condenser should be 1.5 ℃~3 ℃; the shell and tube condenser to be taken at 4 ℃ ~6 ℃.
3, the heat transfer coefficient of the condenser and heat flux density should be according to the product manufacturers to provide data using.
4, on the use of hydrogen fluoride and their mixture as refrigerant, cold storage should be chosen in small air-cooled condenser.